■ rittal fan Product description
Fan-and-filter units with diagonal fan technology have superior pressure stability and ensure a more constant air throughput. The diagonal direction of outflow ensures more even heat dissipation from the enclosure.
■ rittal fan Colour
RAL7035
■ rittal fan Supply includes
Complete unit ready to install, including chopped-fibre filter mat
Fan
■ rittal fan Axial, DC motor
■ rittal fan Air throughput, unimpeded airflow (with chopped-fibre filter)
At 50 Hz: 52m3/h
■ rittal fan Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 63m3/h
■ rittal fan Air throughput with outlet filter including chopped-fibre filter mat (quantity x order number)
1 x 3238200: 36 m3/h
2 x 3238200: 46 m3/h
■ rittal fanRated operating voltage
24 V (DC)
■ rittal fanPower consumption Pel
With DC: 5.5 W
■ rittal fanated Rcurrent max.
With DC: 0.32 A
■ rittal fanDimensions
Width: 148.5 mm
Height: 148.5 mm
■ rittal fan Mounting cut-out
Cut-out width: 124 mm
Cut-out height: 124 mm
■ rittal fan Installation depth
58.5 mm
IP protection category to IEC 60 529
IP54 with chopped-fibre filter/pleated filter
IP56 with chopped-fibre filter/pleated filter and hose-proof hood
Protection category NEMA
Type 12 with chopped-fibre filter/pleated filter
Type 3, 3R, 4, 4X with chopped-fibre filter/pleated filter and hose-proof hood
■ rittal fan Pre-fuse
Miniature circuit-breaker/fuse: 2 A
Note
To increase the air throughput, a pleated filter may optionally be used (see characteristic curve). Suitable for use with fan-and-filter units, roof-mounted fans and outlet filters.
With the fan-and-filter unit 3237.XXX, electrical connection is made via two single wires (length approx. 300 mm) on the unit, for all other fan-and-filter units, a screwless spring terminal is used
■ rittal fan Operating temperature range
-15 °C...55 °C
■ rittal fan Storage temperature range
-30 °C...70 °C
■ rittal fan Noise level
With DC: 46 dB(A)
Packs of
1 pc(s).
Weight/pack
0.54 kg