For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages.
IP 24
IP 54 (electrics)
Cooling output Tw10 Tu32/50 Hz: 2.87 kW
Cooling output Tw10 Tu32/60 Hz: 2.77 kW
Cooling output Tw18 Tu32/50 Hz: 4.18 kW
Cooling output Tw18 Tu32/60 Hz: 4.08 kW
Cooling output Tw18 Tu35/50 Hz: 4 kW
Cooling output Tw18 Tu35/60 Hz: 3.9 kW
Air throughput at 50 Hz: 1,850 m3/h
Air throughput at 60 Hz: 1,850 m3/h
380 V - 415 V, 3~, 50 Hz
440 V - 480 V, 3~, 60 Hz
Width: 450 mm
Height: 820 mm
Depth: 710 mm
By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions.
e+ controller (factory setting +20 °C)
-5 °C...50 °C
-40 °C...70 °C
5 °C...35 °C
± 0.5 K
Refrigerant: R134a
Quantity: 0.76 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 1.09 t
At 50 Hz: 2.9 bar
At 50 Hz: 15 l/min
At 60 Hz: 30 l/min
At 50 Hz: 2.49 kW
At 60 Hz: 2.72 kW
At 50 Hz: 3.95 A
At 60 Hz: 3.47 A
Miniature circuit-breaker/fuse: 15 A
2.8
hermetically open
¾" internal thread
1
Material: PE plastic
Volume: 12 l